iZaⅡ Series

Brochure (Inverter Drive Compressor iZαⅡ Series)

Features

KOBELCO Screw Refrigeration Compressors Always Leading the Times

As a pioneer of screw refrigeration compressors, KOBELCO has taken the lead in the industrial all along, responding to customer's needs always with innovative ideas and proposals. As the new generational of conventional fixed speed drive model SH series, KOBELCO has developed iZ series in 2002, the world first Integral Two Stage Inverter Drive Freon Screw Compressor condensing units with higher cooling capacity than ever before. This series was followed in 2003 by iZα series of an epoch making non-ozone-depleting compressor condensing unit models using refrigerant R404A. iZαⅡ series is iZα series second generation equipped with "New iZ monitor"

With maximized freezing capacity combined with outstanding energy-saving performance in an unheard-of way, iZα series compressor condensing units are being highly acclaimed by customers. KOBELCO's unique theory and technology (patent acquired) that backed iZ and iZα series have received high praise in various industrial circles, being granted the Technology Award from the Japan Society of Refrigeration and Air Conditioning Engineers and the Japan Machinery Federation's Best Energy-saving Equipment Award.

We pursue untiring efforts towards development of earth-friendly products and continue being all attentions to our customer's voice so that we can offer such safe products that can be used with peace of mind while meeting the diversified needs of customers.

Refrigerant R404A does not deplete the OZONE layer.

Since the production of specified ozone-depleting HCFC-based refrigerants (R22) began to be sharply reduced in 2004 and will be completely banned in 2020, a prompt shift to non-ozone-depleting HFC refrigerants is required for compressor condensing units. With zero ozone depleting potential, R404A is a new, environment-friendly HFC refrigerant.

Refrigerant R404A does not deplete the OZONE layer.

The new HFC refrigerant 404A is similar to the conventional HCFC refrigerant 22 in pressure property and easy to use.

  Refrigerant composition ODP Saturation pressure Toxicity Safety
New
HFC R404A
Blended refrigerant
(Pseudo-azeotropic mixture)
(HFC125: 143a: 134a=44: 52: 4 wt%)
zero 2.3MPa Non-toxic
Conventional
HCFC R22
Non-blended refrigerant(100 wt%) 0.055 1.9MPa Non-toxic
* The above saturation pressure values are measured at standard condensation temperature of 50°C.

Kobelco's five big features.

1. Outstanding energy saving performance by Kobelco inverter drive compressor.

iZαⅡ series can control its cooling capacity with its inverter drive linear speed control to avoid excessive cooling, thereby permitting outstanding energy saving performance.

Piston valve used for capacity control has been replaced to inverter drive capacity control to ensure optimum operation in accordance with cooling capacity fluctuation.

Outstanding energy saving performance
Outstanding energy saving performance

2. Maximum 40% increasable cooling capacity by accelerating rotating speed by inverter drive

(compared with Kobelco conventional model in 50Hz area)

patent registered No. 3950304 US Patent #6484522

Conventional refrigeration compressor has been unavoidable to reduce cooling capacity significantly accompany with evaporating temperature drops. Accelerating motor speed technology with inverter drive (Patent registered) enable iZαⅡ series increase its cooling capacity at lower temperature than -30°C .

iZαⅡ series can perform equally in both of 50Hz and 60Hz area, which is a big merit for 50Hz area users where 20% less performance than 60Hz area has been unavoidable. Those functions enable to select smaller compressor than before.

iZαⅡ Series motor speed accelerates accompany with evaporative temperature drop.

iZαⅡ Series motor speed accelerates accompany with evaporative temperature drop.
iZαⅡ Series motor speed accelerates accompany with evaporative temperature drop.

3. "New iZ monitor" with various function for quick and advance trouble shooting.

New iZ monitor indicates compressor running conditions, various alarms and those histories. Also stops compressor automatically against emergency waning.

  • Alternative running applications
    Alternative linear capacity control or step capacity control can be selected due to clients demands.
  • Suction pressure / Remote temperature capacity control
    Linear capacity control with originally equipped suction pressure sensor and also optionally installed temperature sensor (requested users to supply) at freezing site are available.
  • Additional indication
    Super heat is added to monitor compressor situation more clearly.
  • Linear capacity control
    Inverter fixes its rotating speed sensing with originally equipped suction pressure sensor otherwise optionally equipped temperature sensor (the sensor and 4-20mA DC signal are requested users to supply) at freezing site. Controlling factor of suction pressure at the freezing site is requested to preset.
  • Step control
    Capacity step control function is also equipped with iZ monitor, its setting value is available to change flexibly.
New iZ monitor
Compressor protective functions:
  • Discharge temperature
  • Oil pressure differential
  • Discharge pressure
  • Over current
  • Motor temperature

4. Merits of motor start up by inverter drive

Smooth motor startup by inveter drive eliminates inrush current and hot start

The effect of equipped inverter drive can be found when to startup compressor. Since conventional star-delta startup induces inrush current and requires approx 10 minutes interval before restarting. Thanks to the equipped inverter that allows smooth starting, iZαⅡ series can restart quickly without any interval. The smooth starting mechanism permits compressor to stop even in the conventional condition of interruption is not allowed. This mechanism enables more effective energy saving and down sizing of the power facility.

Merits of motor start up by inverter drive

5. Multiple effects created by economizer and inverter drive harmony

iZαⅡ series is equipped economizer regularly and controlled rotating speed of its 1st and 2nd stage by inverter drive. If 1st and 2nd stages do not change their rotating speed at once properly economizer cannot perform properly because pressure unbalance among 1st, middle and 2nd stage caused. iZαⅡ series can control rotating speed flexibly and perfectly always to supply the best performance.

Multiple effects created by economizer and inverter drive harmony

Specification

Water-cooled Standard Specifications (-30°C to -65°C)

Unit type
Item
iZα30WⅡ iZα40WⅡ iZα50WⅡ iZα70WⅡ iZα80WⅡ iZα90WⅡ iZα110WⅡ
Frequency 50/60Hz
Legal ton of refrigeration (JRT) 7.07 9.90 12.17 12.22 15.37 16.95 20.47
Refrigerant R404A
Power source Motor: 200/220/380/400/415/440/460/480, 3 phase. 50/60Hz, Control circuit: 200 to 230V, 1 phase, 50/60Hz
Number of compressors 1 Unit
Capacity control *1*2*3 Continuous control mode or step control mode (3 steps: 50%, 75% and 100%)
Motor Nominal output kW 18 24 30 37 45 55 65
Type Water-cooled semi-hermetic; 4-pole; 3-phase induction type
Starting method Inverter
Condenser Type Horizontal shell and tube (serving also as a receiver)
Receiver capacity ℓ 35 35 35 58 161 76 76
Refrigerant spatial volume ℓ*4 91 91 89 145 231 220 220
Connections Refrigerant gas inlet 50A 50A 50A 80A 80A 80A 100A
Refrigerant liquid outlet 19.05mm 25.4mm 25.4mm 31.8mm 31.8mm 31.8mm 34.9mm
Cooling water inlet/outlet Condenser Rc2 Rc2 Rc2 Rc3 Rc3 Rc3 Rc3
Oil cooler Oil coolerless specification Rc1 Rc1 Rc1 Rc1
Motor Rc1 Rc1 Rc1 Rc1 Rc1 Rc1 Rc1
Lubricating oil ℓ*5 10 10 13 14 21 22 29
Noise dB(A)*6 71 73 75 75 75 79 78
Dimensions
W x D x H mm
1380 x
1110 x
1320
1380 x
1110 x
1320
1405 x
1150 x
1365
1675 x
1200 x
1425
2490 x
1265 x
1525
2485 x
1260 x
1555
2485 x
1290 x
1560
Weight kg 825 840 885 1245 1460 1485 1825
Unit type
Item
iZα140WⅡ iZα160WⅡ iZα180WⅡ iZα220WⅡ iZα280WⅡ iZα320WⅡ
Frequency 50/60Hz
Legal ton of refrigeration (JRT) 24.90 29.34 33.90 40.94 49.80 58.68
Refrigerant R404A
Power source Motor: 200/220/380/400/415/440/460/480, 3 phase, 50/60Hz, Control circuit: 200 - 230V, 1 phase, 50/60Hz
Number of compressors 1 Unit 2 Units
Capacity control *1*2*3 Continuous control mode or step control mode (3 steps: 50%, 75% and 100%)
Motor Nominal output kW 75 90 55 x 2 65 x 2 75 x 2 90 x 2
Type Water-cooled semi-hermetic; 4-pole; 3-phase induction type
Starting method Inverter
Condenser Type Horizontal shell and tube (serving also as a receiver)
Receiver capacity ℓ 183 183 278 278 398 398
Refrigerant spatial volume ℓ*4 278 278 434 434 562 562
Connections Refrigerant gas inlet 100A 100A 80A x 2 100A x 2 100A x 2 100A x 2
Refrigerant liquid outlet 38.1mm 38.1mm 40A 40A 50A 50A
Cooling water inlet/outlet Condenser Rc3 Rc3 Rc4 Rc4 150A 150A
Oil cooler Rc1 Rc1 Rc1 x 2 Rc1 x 2 Rc1 x 2 Rc1 x 2
Motor Rc1 Rc1 Rc1 x 2 Rc1 x 2 Rc1 x 2 Rc1 x 2
Lubricating oil ℓ*5 29 53 53 60 84 84
Noise dB(A)*6 79 82 82 81 82 85
Dimensions W x D x H mm 3000 x
1320 x
1720
3000 x
1420 x
1765
3025 x
1970 x
1750
3025 x
2055 x
1790
2960 x
2140 x
1890
2960 x
2140 x
1890
Weight kg 1930 2020 2710 3300 4380 4440
*1: The minimum capacity depends on production range and operation conditions (25%-50%)
*2: Requested to enter proper signal due to selected running mode.
*3: Partial loading value for step control is changeable flexibly.
*4. Condenser spatial volume for refrigerant is calculated by subtracting the volume of the heat exchanger tube from the inside volume of the condenser.
*5: Oil quantity is minimum charge only for condensing unit. Actual oil quantity for whole of the plant (system) should be determined at the site referring the oil level of sight glasses during compressor running. Charge oil on site and replenish when the level gets lower than requested. Use specified refrigerant machine oil (Oil is requested users to supply)
*6: Noise level (scale A) indicates the values measured at 1meter away from the compressor and 1meter above from the floor level when the suction pressure saturated temperature is -40°Cwithout any echo influence. In the actual installed conditions the noise level maybe different from indicated value because of the influence of surrounding noise and echo.
* : Hot gas defrost model is available optionally.
* : When suction pressure saturated temperature is required below -50°Cmodification for ultra low temperature with cost up is needed.
* : Noise control and harmonic suppression measurement should be taken as necessary according to respective guidelines.
* : Electric power for control circuit is requested users to supply.

Cooling capacity (kW)

Refrigerant: R404A

Condensing
temperature
°C
Saturated temp. at suction press.
°C
iZα
30WⅡ
iZα
40WⅡ
iZα
50WⅡ
iZα
70WⅡ
iZα
80WⅡ
iZα
90WⅡ
iZα
110WⅡ
iZα
140WⅡ
iZα
160WⅡ
iZα
180WⅡ
iZα
220WⅡ
iZα
280WⅡ
iZα
320WⅡ
35 -30 37.1 53.3 67.1 77.0 97.4 107.9 128.1 159.0 185.6 215.8 256.2 318.0 371.2
-35 34.5 49.2 62.1 71.0 90.0 99.9 118.1 146.7 171.4 199.8 236.2 293.4 342.8
-40 31.3 44.9 56.6 63.3 80.3 89.0 105.5 131.3 153.2 178.0 211.0 262.6 306.4
-45 27.1 39.1 49.3 54.8 69.6 77.0 91.7 113.8 133.1 154.0 183.4 227.6 266.2
-50 22.5 32.8 41.1 45.9 58.5 64.6 77.2 96.3 112.1 129.2 154.4 192.6 224.2
-55 18.3 27.3 34.3 37.5 47.7 52.7 63.4 79.0 92.0 105.4 126.8 158.0 184.0
-60 14.3 21.9 27.3 29.9 38.0 42.0 51.1 63.6 74.2 84.0 102.2 127.2 148.4
-65 10.9 17.2 21.7 23.2 29.6 32.3 40.2 50.1 57.7 64.6 80.4 100.2 115.4
40 -30 36.5 52.6 66.2 75.8 96.2 106.4 126.1 156.3 182.7 212.8 252.2 312.6 365.4
-35 33.9 48.5 61.1 69.9 88.7 98.3 116.2 144.5 169.0 196.6 232.4 289.0 338.0
-40 30.5 43.7 55.1 61.6 78.2 86.6 102.8 127.8 149.5 173.2 205.6 255.6 299.0
-45 26.3 38.0 47.9 53.2 67.6 74.8 89.2 110.8 129.6 149.6 178.4 221.6 259.2
-50 21.9 31.9 39.9 44.6 56.7 62.7 75.3 93.5 109.1 125.4 150.6 187.0 218.2
-55 17.7 26.4 33.2 36.2 46.2 51.0 61.6 76.6 89.2 102.0 123.2 153.2 178.4
-60 13.8 21.1 26.4 28.9 36.7 40.5 49.5 61.7 71.8 81.0 99.0 123.4 143.6
-65 10.5 16.4 20.7 22.2 28.2 30.9 38.8 48.3 55.6 61.8 77.6 96.6 111.2
* : This is the case for superheat 0°C and economizer middle stage evaporative temperature +10°C (iZα30WⅡ, 40WⅡ, 50WⅡ case is +5°C)
* : Please contact Kobelco in case of using suction pressure saturating temperature is less than -50°C

Power consumption (kW)

Condensing
temperature
°C
Saturated temp. at suction press.
°C
iZα
30WⅡ
iZα
40WⅡ
iZα
50WⅡ
iZα
70WⅡ
iZα
80WⅡ
iZα
90WⅡ
iZα
110WⅡ
iZα
140WⅡ
iZα
160WⅡ
iZα
180WⅡ
iZα
220WⅡ
iZα
280WⅡ
iZα
320WⅡ
35 -30 21.2 28.1 32.9 40.3 50.2 55.3 66.8 82.4 94.9 110.6 133.6 164.8 189.8
-35 22.2 30.2 34.2 41.0 51.2 56.2 68.0 83.8 97.4 112.4 136.0 167.6 194.8
-40 22.3 29.9 35.0 40.5 50.5 55.7 67.9 84.5 98.9 111.4 135.8 169.0 197.8
-45 22.7 30.4 34.8 40.3 50.0 55.4 67.7 83.9 98.5 110.8 135.4 167.8 197.0
-50 22.0 29.0 34.0 38.6 48.6 53.6 66.7 82.5 96.7 107.2 133.4 165.0 193.4
-55 22.2 29.0 34.3 37.2 46.7 51.5 65.6 80.0 93.5 103.0 131.2 160.0 187.0
-60 21.4 27.7 31.7 36.1 45.2 49.8 63.8 77.5 90.3 99.6 127.6 155.0 180.6
-65 21.5 27.7 30.0 34.6 42.8 46.9 61.5 75.2 86.0 93.8 123.0 150.4 172.0
40 -30 22.6 30.3 35.0 43.0 54.1 58.8 69.7 86.0 100.6 117.6 139.4 172.0 201.2
-35 23.8 32.1 36.3 43.9 54.3 59.7 70.7 88.2 102.5 119.4 141.4 176.4 205.0
-40 23.9 31.9 37.1 43.5 53.8 59.1 71.6 89.0 104.4 118.2 143.2 178.0 208.8
-45 24.5 32.7 37.2 43.4 53.2 58.5 71.1 88.2 103.9 117.0 142.2 176.4 207.8
-50 23.7 31.1 36.2 41.5 52.0 57.0 70.3 86.7 101.7 114.0 140.6 173.4 203.4
-55 23.9 31.4 36.7 40.1 49.5 55.1 69.1 83.9 98.2 110.2 138.2 167.8 196.4
-60 23.1 29.6 34.3 38.9 48.3 53.8 67.4 81.8 95.0 107.6 134.8 163.6 190.0
-65 23.2 29.8 32.4 37.4 46.1 50.6 65.0 79.5 91.0 101.2 130.0 159.0 182.0

Air-Cooled Standard Specifications (-30°C to -65°C)

Package-Type

Unit type
Item
iZα30AⅡ iZα40AⅡ iZα50AⅡ iZα70AⅡ iZα90AⅡ
Frequency 50/60Hz
Legal ton of refrigeration (JRT) 7.07 9.90 12.17 12.22 17.0
Refrigerant R404A
Power source Motor: 200/220/380/400/415/440/460/480, 3 phase, 50/60Hz, Control circuit: 200 - 230V, 1 phase, 50/60Hz
Number of compressors 1 Unit
Capacity control *1*2*3 Continuous control mode or step control mode (3 steps: 50%, 75% and 100%)
Motor Nominal output kW 18 24 30 37 55
Type Semi-hermetic; 4-pole; 3-phase induction type
Starting method Inverter
Condenser Type Plate fin tube
Air blower output kW x units 0.4 x 2 0.4 x 3 0.75 x 3 0.2 x 6 0.4 x 6
Receiver capacity ℓ 76 109 109 177 235
Lubricating oil ℓ*4 10.0 10 13 13 19
Connections Refrigerant gas inlet 50.8mm 50.8mm 50.8mm 63.5mm 79.4mm
Refrigerant liquid outlet 19.05mm 25.4mm 25.4mm 31.8mm 31.8mm
Installation Outdoor
Noise dB(A)*5 2055 x
1315 x
2255
2865 x
1315 x
2430
2865 x
1315 x
2430
2690 x
1395 x
2705
2690 x
1795 x
2805
Dimensions W x D x H mm 64 65 67 66 70
Weight kg 1400 1635 1700 2025 2330

Separate-type

Unit type
Item
iZα
30ASⅡ
iZα
40ASⅡ
iZα
50ASⅡ
iZα
70ASⅡ
iZα
90ASⅡ
iZα
140ASⅡ
iZα
180ASⅡ
iZα
280ASⅡ
Frequency 50/60Hz
Legal ton of refrigeration (JRT) 7.07 9.90 12.17 12.22 16.95 24.90 33.90 49.80
Refrigerant R404A
Power source Motor: 200/220/380/400/415/440/460/480, 3 phase, 50/60Hz, Control circuit: 200 - 230V, 1 phase, 50/60Hz
Compressor unit Number of compressors 1 Unit 2 Units
Capacity control *1*2*3 Continuous control mode or step control mode (3 steps: 50%, 75% and 100%)
Motor Nominal output kW 18 24 30 37 55 75 55 x 2 75 x 2
Type Semi-hermetic; 4-pole; 3-phase induction type
Starting method Inverter
Receiver capacity ℓ 76 109 109 177 265 380 504 599
Lubricating oil ℓ*4 10 10 13 13 19 25 47 75
Connections Refrigerant gas inlet (suction) 50A 50A 50A 80A 80A 100A 80A x 2 100A x 2
Refrigerant liquid outlet (discharge) 25A 25A 32A 32A 40A 50A 65A 80A
Refrigerant liquid inlet (return) 25.4mm 31.8mm 31.8mm 38.1mm 38.1mm 50A 65A 80A
Refrigerant liquid outlet 19.05mm 25.4mm 25.4mm 31.8mm 31.8mm 38.1mm 40A 50A
Installation Indoor
Dimensions
W x D x H mm
1645 x
1080 x
1125
2235 x
1125 x
1245
2235 x
1160 x
1245
2040 x
1195 x
1415
2300 x
1260 x
1415
3105 x
1300 x
1720
2810 x
1970 x
1645
3300 x
2140 x
1855
Noise dB(A)*5 71 73 75 75 79 79 82 82
Weight kg 795 830 895 1055 1170 1560 2210 3280
Condenser
unit
Type x units VACK24 VACK32 VACK40 WACK50 WACK75 WACK50
x 2units
WACK75
x 2units
WACK50
x 4units
Air blower output KW x units 0.4 x 2 0.4 x 3 0.75 x 3 0.2 x 6 0.4 x 6 0.2 x 6
2units
0.4 x 6
2units
0.2 x 6
4units
Installation Outdoor
Dimensions
W x D x H mm
2085 x
875 x
1175
2845 x
875 x
1175
2845 x
875 x
1175
2670 x
1220 x
1080
2670 x
1620 x
1185
2670 x
1220 x
1080
2units
2670 x
1620 x
1185
2units
2670 x
1220 x
1080
4units
Noise dB(A)*5 63 65 66 65 67 68 70 71
Weight kg 250 340 370 500 530 500
2units
530
2units
500
4units
*1: The minimum capacity depends on production range and operation conditions (25%-50%)
*2: Requested to enter proper signal due to selected running mode.
*3: Partial loading value for step control is changeable flexibly.
*4. Condenser spatial volume for refrigerant is calculated by subtracting the volume of the heat exchanger tube from the inside volume of the condenser.
*5: Oil quantity is minimum charge only for condensing unit. Actual oil quantity for whole of the plant (system) should be determined at the site referring the oil level of sight glasses during compressor running. Charge oil on site and replenish when the level gets lower than requested. Use specified refrigerant machine oil (Oil is requested users to supply)
*6: Noise level (scale A) indicates the values measured at 1meter away from the compressor and 1meter above from the floor level when the suction pressure saturated temperature is -40°Cwithout any echo influence. In the actual installed conditions the noise level maybe different from indicated value because of the influence of surrounding noise and echo.
* : Hot gas defrost model is available optionally.
* : When suction pressure saturated temperature is required below -50°Cmodification for ultra low temperature with cost up is needed.
* : Noise control and harmonic suppression measurement should be taken as necessary according to respective guidelines.
* : Electric power for control circuit is requested users to supply.

Cooling capacity (kW)

Refrigerant: R404A

Ambient
temperature
°C
Saturated temp.
at suction press.
°C
iZα
30AⅡ
iZα
30ASⅡ
iZα
40AⅡ
iZα
40ASⅡ
iZα
50AⅡ
iZα
50ASⅡ
iZα
70AⅡ
iZα
70ASⅡ
iZα
90AⅡ
iZα
90ASⅡ
iZα
140ASⅡ
iZα
180ASⅡ
iZα
280ASⅡ
27 -30 35.7 50.0 62.4 68.1 95.3 140.5 190.6 281.0
-35 32.9 46.3 57.4 64.8 91.0 134.0 182.0 268.0
-40 29.6 41.8 51.9 59.4 83.8 123.4 167.6 246.8
-45 25.7 36.3 44.9 51.5 72.4 107.3 144.8 214.6
-50 21.7 30.7 37.9 43.4 61.0 90.8 122.0 181.6
-55 17.5 24.9 30.8 35.2 49.4 74.2 98.8 148.4
-60 13.9 19.8 24.8 27.9 39.3 59.4 78.6 118.8
-65 11.0 15.6 19.0 21.3 29.6 45.8 59.2 91.6
32 -30 34.2 48.0 59.7 66.1 92.4 135.9 184.8 271.8
-35 32.0 45.0 55.9 62.9 88.1 130.1 176.2 260.2
-40 28.7 40.6 50.3 57.8 81.1 119.9 162.2 239.8
-45 25.0 35.3 43.6 50.1 70.3 104.4 140.6 208.8
-50 21.0 29.6 36.6 42.0 59.0 88.4 118.0 176.8
-55 17.1 24.2 29.9 34.0 47.7 71.9 95.4 143.8
-60 13.5 19.0 23.5 26.3 37.0 56.2 74.0 112.4
-65 10.4 14.7 17.9 19.8 27.6 43.2 55.2 86.4
* : This is the case for superheat 0°C and economizer middle stage evaporative temperature +10°C (iZα30WⅡ, 40WⅡ, 50WⅡ case is +5°C)
* : Please contact Kobelco in case of using suction pressure saturating temperature is less than -50°C

Power consumption (kW)

Ambient
temperature
°C
Saturated temp.
at suction press.
°C
iZα
30AⅡ
iZα
30ASⅡ
iZα
40AⅡ
iZα
40ASⅡ
iZα
50AⅡ
iZα
50ASⅡ
iZα
70AⅡ
iZα
70ASⅡ
iZα
90AⅡ
iZα
90ASⅡ
iZα
140ASⅡ
iZα
180ASⅡ
iZα
280ASⅡ
27 -30 23.8 33.3 38.7 44.1 62.8 89.7 125.6 179.4
-35 23.8 33.3 39.0 45.2 64.4 92.4 128.8 184.8
-40 23.8 33.1 38.9 45.2 64.2 92.8 128.4 185.6
-45 23.3 32.3 38.1 44.2 63.0 90.3 126.0 180.6
-50 22.7 31.5 37.1 42.8 61.0 87.5 122.0 175.0
-55 22.3 31.0 36.0 41.1 58.2 84.6 116.4 169.2
-60 21.8 30.1 34.9 39.0 55.7 80.9 111.4 161.8
-65 20.2 27.8 32.7 37.5 51.8 76.6 103.6 153.2
32 -30 25.3 35.3 41.3 47.7 68.2 97.4 136.4 194.8
-35 25.3 35.4 41.4 49.3 70.2 100.3 140.4 200.6
-40 25.3 35.2 41.3 49.0 69.9 100.3 139.8 200.6
-45 25.2 34.9 41.1 48.2 68.6 98.6 137.2 197.2
-50 24.6 34.1 40.1 46.8 66.2 95.9 132.4 191.8
-55 24.3 33.6 39.6 45.0 63.7 91.9 127.4 183.8
-60 23.7 32.8 38.8 42.9 60.9 87.9 121.8 175.8
-65 22.1 30.5 35.8 41.2 56.6 83.1 113.2 166.2
* : Power consumption of condensing fan in not included.